R-402A PT Chart

R-402A saturation pressure, −40 to 145 °F−40 to 62 °C. Used in R-502 retrofits (HP80).

How to use ↓

Safety class A1Zeotropic blend (low glide)Glide 2.33 °F at 40 °F evapGlide 1.29 K at 4.4 °C evap

PT lookup

Step 2 I know the
°F°C

Type a temperature to see the saturation pressure.

R-402A pressure temperature table

Liquid = bubble (subcooling). Vapor = dew (superheat). Highlighted: 40 °F and 100 °F.Liquid = bubble (subcooling). Vapor = dew (superheat). Negative kPa = vacuum. Highlighted: 4 °C and 38 °C.

The table covers −40 to 145 °F−40 to 62 °C only: the published manufacturer data stops there, and the table is not extrapolated past it.

R-402A saturation pressure by temperature, °F and psig (vacuum in inches of mercury)
°FLiquid bubble, psigVapor dew, psig
-407.45.7
-398.06.2
-388.56.8
-379.17.3
-369.77.8
-3510.38.4
-3410.99.0
-3311.59.6
-3212.110.2
-3112.710.8
-3013.411.4
-2914.012.0
-2814.712.6
-2715.413.3
-2616.114.0
-2516.814.6
-2417.515.3
-2318.216.0
-2219.016.7
-2119.717.4
-2020.518.2
-1921.218.9
-1822.019.7
-1722.820.5
-1623.721.3
-1524.522.1
-1425.322.9
-1326.223.7
-1227.124.6
-1128.025.4
-1028.926.3
-929.827.2
-830.728.1
-731.729.0
-632.629.9
-533.630.9
-434.631.8
-335.632.8
-236.633.8
-137.734.8
038.735.8
139.836.9
240.937.9
342.039.0
443.140.1
544.241.2
645.442.3
746.643.4
847.744.6
949.045.8
1050.246.9
1151.448.2
1252.749.4
1353.950.6
1455.251.9
1556.653.2
1657.954.5
1759.255.8
1860.657.1
1962.058.5
2063.459.8
2164.861.2
2266.362.6
2367.764.1
2469.265.5
2570.767.0
2672.268.5
2773.870.0
2875.471.5
2976.973.1
3078.574.7
3180.276.3
3281.877.9
3383.579.5
3485.281.2
3586.982.8
3688.684.5
3790.486.3
3892.288.0
3994.089.8
4095.891.6
4197.793.4
4299.595.2
43101.497.1
44103.399.0
45105.3100.9
46107.2102.8
47109.2104.8
48111.2106.8
49113.3108.8
50115.3110.8
51117.4112.9
52119.5114.9
53121.7117.0
54123.8119.2
55126.0121.3
56128.3123.5
57130.5125.7
58132.8128.0
59135.0130.2
60137.4132.5
61139.7134.8
62142.1137.2
63144.5139.5
64146.9141.9
65149.4144.4
66151.8146.8
67154.4149.3
68156.9151.8
69159.5154.3
70162.1156.9
71164.7159.5
72167.3162.1
73170.0164.8
74172.7167.5
75175.5170.2
76178.2172.9
77181.0175.7
78183.9178.5
79186.7181.3
80189.6184.2
81192.5187.1
82195.5190.0
83198.5193.0
84201.5196.0
85204.5199.0
86207.6202.0
87210.7205.1
88213.9208.3
89217.0211.4
90220.2214.6
91223.5217.8
92226.8221.1
93230.1224.4
94233.4227.7
95236.8231.0
96240.2234.4
97243.6237.9
98247.1241.3
99250.6244.8
100254.2248.4
101257.8251.9
102261.4255.5
103265.0259.2
104268.7262.8
105272.5266.6
106276.2270.3
107280.0274.1
108283.9277.9
109287.7281.8
110291.7285.7
111295.6289.6
112299.6293.6
113303.6297.6
114307.7301.7
115311.8305.8
116315.9309.9
117320.1314.1
118324.3318.3
119328.6322.6
120332.9326.9
121337.3331.2
122341.6335.6
123346.1340.0
124350.5344.5
125355.0349.0
126359.6353.6
127364.2358.2
128368.8362.8
129373.5367.5
130378.2372.2
131383.0377.0
132387.8381.8
133392.6386.6
134397.5391.5
135402.4396.5
136407.4401.5
137412.4406.5
138417.5411.6
139422.6416.8
140427.8421.9
141433.0427.2
142438.2432.4
143443.5437.8
144448.9443.1
145454.3448.5
R-402A saturation pressure by temperature, °C and kPa (negative = vacuum)
°CLiquid bubble, kPaVapor dew, kPa
-4051.339.4
-3958.145.9
-3865.152.6
-3772.459.5
-3680.066.7
-3587.874.2
-3495.881.9
-33104.189.8
-32112.798.1
-31121.5106.5
-30130.7115.3
-29140.1124.4
-28149.8133.7
-27159.8143.3
-26170.1153.2
-25180.7163.5
-24191.6174.0
-23202.8184.8
-22214.4196.0
-21226.3207.5
-20238.5219.4
-19251.1231.6
-18264.0244.1
-17277.3257.0
-16291.0270.2
-15305.0283.9
-14319.4297.8
-13334.2312.2
-12349.3327.0
-11364.9342.1
-10380.9357.7
-9397.2373.7
-8414.0390.1
-7431.2406.9
-6448.9424.1
-5467.0441.8
-4485.5459.9
-3504.5478.4
-2523.9497.4
-1543.8516.9
0564.2536.9
1585.0557.3
2606.3578.2
3628.1599.6
4650.5621.6
5673.3644.0
6696.6666.9
7720.5690.4
8744.9714.4
9769.8738.9
10795.3764.0
11821.3789.6
12847.9815.8
13875.1842.6
14902.8869.9
15931.1897.9
16960.0926.4
17989.5955.5
181019.7985.3
191050.41015.7
201081.71046.7
211113.71078.3
221146.31110.6
231179.61143.5
241213.51177.1
251248.11211.4
261283.41246.3
271319.41281.9
281356.01318.3
291393.31355.3
301431.41393.1
311470.21431.6
321509.71470.8
331549.91510.8
341590.91551.5
351632.61593.0
361675.11635.2
371718.31678.3
381762.41722.1
391807.21766.8
401852.91812.2
411899.31858.5
421946.61905.7
431994.71953.6
442043.62002.4
452093.42052.1
462144.12102.7
472195.62154.2
482248.02206.5
492301.32259.8
502355.52314.0
512410.62369.1
522466.62425.2
532523.62482.2
542581.52540.2
552640.42599.1
562700.22659.1
572761.02720.1
582822.82782.1
592885.72845.1
602949.52909.1
613014.32974.2
623080.23040.4
Back to the lookup ↑

R-402A PT Chart

°F / psig · Safety class A1 · Zeotropic blend (low glide)

refrigerantptchart.com

°FLiquidVapor
-407.45.7
-398.06.2
-388.56.8
-379.17.3
-369.77.8
-3510.38.4
-3410.99.0
-3311.59.6
-3212.110.2
-3112.710.8
-3013.411.4
-2914.012.0
-2814.712.6
-2715.413.3
-2616.114.0
-2516.814.6
-2417.515.3
-2318.216.0
-2219.016.7
-2119.717.4
-2020.518.2
-1921.218.9
-1822.019.7
-1722.820.5
-1623.721.3
-1524.522.1
-1425.322.9
-1326.223.7
-1227.124.6
-1128.025.4
-1028.926.3
-929.827.2
-830.728.1
-731.729.0
-632.629.9
-533.630.9
-434.631.8
-335.632.8
-236.633.8
-137.734.8
038.735.8
139.836.9
240.937.9
342.039.0
443.140.1
544.241.2
645.442.3
°FLiquidVapor
746.643.4
847.744.6
949.045.8
1050.246.9
1151.448.2
1252.749.4
1353.950.6
1455.251.9
1556.653.2
1657.954.5
1759.255.8
1860.657.1
1962.058.5
2063.459.8
2164.861.2
2266.362.6
2367.764.1
2469.265.5
2570.767.0
2672.268.5
2773.870.0
2875.471.5
2976.973.1
3078.574.7
3180.276.3
3281.877.9
3383.579.5
3485.281.2
3586.982.8
3688.684.5
3790.486.3
3892.288.0
3994.089.8
4095.891.6
4197.793.4
4299.595.2
43101.497.1
44103.399.0
45105.3100.9
46107.2102.8
47109.2104.8
48111.2106.8
49113.3108.8
50115.3110.8
51117.4112.9
52119.5114.9
53121.7117.0
°FLiquidVapor
54123.8119.2
55126.0121.3
56128.3123.5
57130.5125.7
58132.8128.0
59135.0130.2
60137.4132.5
61139.7134.8
62142.1137.2
63144.5139.5
64146.9141.9
65149.4144.4
66151.8146.8
67154.4149.3
68156.9151.8
69159.5154.3
70162.1156.9
71164.7159.5
72167.3162.1
73170.0164.8
74172.7167.5
75175.5170.2
76178.2172.9
77181.0175.7
78183.9178.5
79186.7181.3
80189.6184.2
81192.5187.1
82195.5190.0
83198.5193.0
84201.5196.0
85204.5199.0
86207.6202.0
87210.7205.1
88213.9208.3
89217.0211.4
90220.2214.6
91223.5217.8
92226.8221.1
93230.1224.4
94233.4227.7
95236.8231.0
96240.2234.4
97243.6237.9
98247.1241.3
99250.6244.8
100254.2248.4
°FLiquidVapor
101257.8251.9
102261.4255.5
103265.0259.2
104268.7262.8
105272.5266.6
106276.2270.3
107280.0274.1
108283.9277.9
109287.7281.8
110291.7285.7
111295.6289.6
112299.6293.6
113303.6297.6
114307.7301.7
115311.8305.8
116315.9309.9
117320.1314.1
118324.3318.3
119328.6322.6
120332.9326.9
121337.3331.2
122341.6335.6
123346.1340.0
124350.5344.5
125355.0349.0
126359.6353.6
127364.2358.2
128368.8362.8
129373.5367.5
130378.2372.2
131383.0377.0
132387.8381.8
133392.6386.6
134397.5391.5
135402.4396.5
136407.4401.5
137412.4406.5
138417.5411.6
139422.6416.8
140427.8421.9
141433.0427.2
142438.2432.4
143443.5437.8
144448.9443.1
145454.3448.5

Liquid = bubble (use for subcooling). Vapor = dew (use for superheat). Bold rows: 40 °F and 100 °F. Reference only: always verify with the manufacturer’s data and your gauges.

R-402A PT Chart

°C / kPa (gauge) · Safety class A1 · Zeotropic blend (low glide)

refrigerantptchart.com

°CLiquidVapor
-4051.339.4
-3958.145.9
-3865.152.6
-3772.459.5
-3680.066.7
-3587.874.2
-3495.881.9
-33104.189.8
-32112.798.1
-31121.5106.5
-30130.7115.3
-29140.1124.4
-28149.8133.7
-27159.8143.3
-26170.1153.2
-25180.7163.5
-24191.6174.0
-23202.8184.8
-22214.4196.0
-21226.3207.5
-20238.5219.4
-19251.1231.6
-18264.0244.1
-17277.3257.0
-16291.0270.2
-15305.0283.9
-14319.4297.8
-13334.2312.2
-12349.3327.0
-11364.9342.1
-10380.9357.7
-9397.2373.7
-8414.0390.1
-7431.2406.9
-6448.9424.1
°CLiquidVapor
-5467.0441.8
-4485.5459.9
-3504.5478.4
-2523.9497.4
-1543.8516.9
0564.2536.9
1585.0557.3
2606.3578.2
3628.1599.6
4650.5621.6
5673.3644.0
6696.6666.9
7720.5690.4
8744.9714.4
9769.8738.9
10795.3764.0
11821.3789.6
12847.9815.8
13875.1842.6
14902.8869.9
15931.1897.9
16960.0926.4
17989.5955.5
181019.7985.3
191050.41015.7
201081.71046.7
211113.71078.3
221146.31110.6
231179.61143.5
241213.51177.1
251248.11211.4
261283.41246.3
271319.41281.9
281356.01318.3
291393.31355.3
°CLiquidVapor
301431.41393.1
311470.21431.6
321509.71470.8
331549.91510.8
341590.91551.5
351632.61593.0
361675.11635.2
371718.31678.3
381762.41722.1
391807.21766.8
401852.91812.2
411899.31858.5
421946.61905.7
431994.71953.6
442043.62002.4
452093.42052.1
462144.12102.7
472195.62154.2
482248.02206.5
492301.32259.8
502355.52314.0
512410.62369.1
522466.62425.2
532523.62482.2
542581.52540.2
552640.42599.1
562700.22659.1
572761.02720.1
582822.82782.1
592885.72845.1
602949.52909.1
613014.32974.2
623080.23040.4

Liquid = bubble (use for subcooling). Vapor = dew (use for superheat). Bold rows: 4 °C and 38 °C. Reference only: always verify with the manufacturer’s data and your gauges.

How to use

  1. Choose Temperature or Pressure and type the number. The answer shows straight away.
  2. Blends show two values: use vapor (dew) for superheat and liquid (bubble) for subcooling.
  3. Tap °C · kPa for metric. Below 0 psig, pressure is in inches of mercury (inHg) vacuum.
  4. Press Print pocket chart for a one-page chart (Letter or A4) for the van or the tool bag.

Back to top ↑

About this R-402A chart

This R-402A pressure temperature chart gives the saturation pressure for every degree, in psig with °F or kPa (gauge) with °C. As a blend, it has a liquid (bubble) and a vapor (dew) column.

Source: manufacturer and supplier charts (Honeywell, Arkema, National Refrigerants). Reference only: always verify with the manufacturer’s data and your gauges.

FAQ

What is the R-402A pressure at 40 °F?

91.6 psig vapor (dew) and 95.8 psig liquid (bubble) at saturation, from the table above.

What is the R-402A pressure at 100 °F?

248.4 psig vapor (dew) and 254.2 psig liquid (bubble) at saturation.

Which column do I use for superheat and subcooling?

Use vapor (dew) for superheat and liquid (bubble) for subcooling. R-402A has 2.33 °F of glide at a 40 °F evaporator, so the two columns differ.

Coming from Check & Charge or PT Pro? See the free offline alternative (no login).

Related