Superheat & Subcooling Calculator

Enter a line pressure and temperature. Get superheat or subcooling for 43 refrigerants, including R-410A, R-404A, R-134a and R-22.

How to use ↓

Calculator

Step 2 Checking
kPabar
°F°C

Enter the pressure and the line temperature.

Next

How to use

  1. Pick the refrigerant and choose Superheat or Subcooling.
  2. Superheat: suction pressure, and the suction line temperature near the evaporator outlet or the compressor.
  3. Subcooling: liquid line pressure, and the liquid line temperature near the condenser outlet.
  4. Compare with the target on the equipment’s charging chart or the manufacturer’s instructions.

Back to top ↑

Worked examples

These are example readings to show the math. They are not targets, and they are not what any particular system should read. Each saturation temperature comes from the same tables the calculator uses.

Superheat examples

Superheat = suction line temperature minus saturation (dew) temperature at the suction pressure
RefrigerantSuction pressureSaturation tempSuction line tempSuperheat
R-410A118 psig39.8 °F (dew)52 °F12.2 °F
R-2268 psig39.6 °F50 °F10.4 °F
R-134a30 psig34.6 °F45 °F10.4 °F
R-404A55 psig19.8 °F (dew)30 °F10.2 °F
R-407C70 psig44.5 °F (dew)52 °F7.5 °F

Take the R-410A line. At 118 psig the dew temperature is 39.8 °F. The suction line reads 52 °F, so the vapor has picked up 12.2 °F above saturation. That’s the superheat.

R-22 and R-134a are single refrigerants, so there’s only one saturation temperature at each pressure. R-404A, R-410A and R-407C are blends, and the calculator uses the dew column for superheat.

Subcooling examples

Subcooling = saturation (bubble) temperature at the liquid pressure minus liquid line temperature
RefrigerantLiquid pressureSaturation tempLiquid line tempSubcooling
R-410A340 psig104.6 °F (bubble)95 °F9.6 °F
R-404A250 psig103.8 °F (bubble)95 °F8.8 °F
R-134a150 psig111.5 °F100 °F11.5 °F

Why the dew column matters on blends

R-407C has a lot of glide. At 70 psig its dew temperature is 44.5 °F and its bubble temperature is 33.6 °F. With a 52 °F suction line, the dew value gives 7.5 °F of superheat. Read the bubble value by mistake and you’d get 18.4 °F, more than double. On a near-azeotropic blend like R-404A the gap is small (19.8 °F dew vs 18.8 °F bubble at 55 psig), but it still adds up to a degree. Working on a walk-in? See R-404A pressures on walk-in coolers and freezers.

How it works

Superheat is the line temperature minus the saturation temperature at the suction pressure. Subcooling is the saturation temperature at the liquid pressure minus the line temperature. For blends the calculator uses the vapor (dew) value for superheat and the liquid (bubble) value for subcooling, from the same tables as the PT charts.

Preparing for Section 608? See EPA 608 Universal certification: test format and cost.

FAQ

Why dew for superheat and bubble for subcooling?

Blends with glide boil and condense over a range. Vapor in the suction line leaves at the dew point; liquid leaving the condenser starts at the bubble point.

What does a negative result mean?

Usually a reading is off, the probe is in the wrong place, or the wrong refrigerant is picked. Check the gauges and the thermometer first.

Does it work as an R-404A or R-134a superheat calculator?

Yes. Pick R-404A, R-134a or any of the other 43 refrigerants from the list. The R-404A and R-134a rows in the examples above show the same math done by hand.

What superheat or subcooling should I aim for?

It depends on the system and its metering device. Use the target from the equipment’s charging chart or the manufacturer’s instructions.

For a worked example of reading the chart by hand, see how to read a PT chart.