R-134a PT Chart
R-134a saturation pressure, −40 to 150 °F−40 to 65 °C. Used in domestic refrigerators, vending, chillers and automotive A/C.
How to use ↓Download, share or get updates ↓
Safety class A1Single component (HFC)No glideNo glide
Type a temperature to see the saturation pressure.
Below 0 psig: inches of mercury vacuum. Highlighted: 40 °F and 100 °F. Gauge pressures assume sea-level air (14.7 psia / 101.3 kPa). At altitude your gauge reads higher for the same temperature, about 2.5 psi at 5,000 ft. Negative kPa(g) = vacuum. Highlighted: 4 °C and 38 °C. Gauge pressures assume sea-level air (14.7 psia / 101.3 kPa). At altitude your gauge reads higher for the same temperature, about 2.5 psi at 5,000 ft.
| °F | Pressure psig |
|---|---|
| -40 | 14.8 inHg |
| -39 | 14.4 inHg |
| -38 | 13.9 inHg |
| -37 | 13.4 inHg |
| -36 | 13.0 inHg |
| -35 | 12.5 inHg |
| -34 | 12.0 inHg |
| -33 | 11.4 inHg |
| -32 | 10.9 inHg |
| -31 | 10.4 inHg |
| -30 | 9.8 inHg |
| -29 | 9.3 inHg |
| -28 | 8.7 inHg |
| -27 | 8.1 inHg |
| -26 | 7.5 inHg |
| -25 | 6.9 inHg |
| -24 | 6.3 inHg |
| -23 | 5.7 inHg |
| -22 | 5.0 inHg |
| -21 | 4.3 inHg |
| -20 | 3.7 inHg |
| -19 | 3.0 inHg |
| -18 | 2.3 inHg |
| -17 | 1.5 inHg |
| -16 | 0.8 inHg |
| -15 | 0.0 |
| -14 | 0.4 |
| -13 | 0.7 |
| -12 | 1.1 |
| -11 | 1.5 |
| -10 | 1.9 |
| -9 | 2.4 |
| -8 | 2.8 |
| -7 | 3.2 |
| -6 | 3.6 |
| -5 | 4.1 |
| -4 | 4.6 |
| -3 | 5.0 |
| -2 | 5.5 |
| -1 | 6.0 |
| 0 | 6.5 |
| 1 | 7.0 |
| 2 | 7.5 |
| 3 | 8.0 |
| 4 | 8.5 |
| 5 | 9.1 |
| 6 | 9.6 |
| 7 | 10.2 |
| 8 | 10.8 |
| 9 | 11.3 |
| 10 | 11.9 |
| 11 | 12.5 |
| 12 | 13.1 |
| 13 | 13.8 |
| 14 | 14.4 |
| 15 | 15.0 |
| 16 | 15.7 |
| 17 | 16.4 |
| 18 | 17.0 |
| 19 | 17.7 |
| 20 | 18.4 |
| 21 | 19.1 |
| 22 | 19.9 |
| 23 | 20.6 |
| 24 | 21.3 |
| 25 | 22.1 |
| 26 | 22.9 |
| 27 | 23.7 |
| 28 | 24.5 |
| 29 | 25.3 |
| 30 | 26.1 |
| 31 | 26.9 |
| 32 | 27.8 |
| 33 | 28.6 |
| 34 | 29.5 |
| 35 | 30.4 |
| 36 | 31.3 |
| 37 | 32.2 |
| 38 | 33.1 |
| 39 | 34.1 |
| 40 | 35.0 |
| 41 | 36.0 |
| 42 | 37.0 |
| 43 | 38.0 |
| 44 | 39.0 |
| 45 | 40.1 |
| 46 | 41.1 |
| 47 | 42.2 |
| 48 | 43.2 |
| 49 | 44.3 |
| 50 | 45.4 |
| 51 | 46.6 |
| 52 | 47.7 |
| 53 | 48.9 |
| 54 | 50.0 |
| 55 | 51.2 |
| 56 | 52.4 |
| 57 | 53.6 |
| 58 | 54.9 |
| 59 | 56.1 |
| 60 | 57.4 |
| 61 | 58.7 |
| 62 | 60.0 |
| 63 | 61.3 |
| 64 | 62.7 |
| 65 | 64.0 |
| 66 | 65.4 |
| 67 | 66.8 |
| 68 | 68.2 |
| 69 | 69.7 |
| 70 | 71.1 |
| 71 | 72.6 |
| 72 | 74.1 |
| 73 | 75.6 |
| 74 | 77.1 |
| 75 | 78.7 |
| 76 | 80.2 |
| 77 | 81.8 |
| 78 | 83.4 |
| 79 | 85.0 |
| 80 | 86.7 |
| 81 | 88.4 |
| 82 | 90.0 |
| 83 | 91.8 |
| 84 | 93.5 |
| 85 | 95.2 |
| 86 | 97.0 |
| 87 | 98.8 |
| 88 | 100.6 |
| 89 | 102.5 |
| 90 | 104.3 |
| 91 | 106.2 |
| 92 | 108.1 |
| 93 | 110.0 |
| 94 | 112.0 |
| 95 | 113.9 |
| 96 | 115.9 |
| 97 | 118.0 |
| 98 | 120.0 |
| 99 | 122.1 |
| 100 | 124.2 |
| 101 | 126.3 |
| 102 | 128.4 |
| 103 | 130.6 |
| 104 | 132.7 |
| 105 | 135.0 |
| 106 | 137.2 |
| 107 | 139.5 |
| 108 | 141.7 |
| 109 | 144.0 |
| 110 | 146.4 |
| 111 | 148.7 |
| 112 | 151.1 |
| 113 | 153.5 |
| 114 | 156.0 |
| 115 | 158.4 |
| 116 | 160.9 |
| 117 | 163.4 |
| 118 | 166.0 |
| 119 | 168.6 |
| 120 | 171.2 |
| 121 | 173.8 |
| 122 | 176.5 |
| 123 | 179.1 |
| 124 | 181.8 |
| 125 | 184.6 |
| 126 | 187.4 |
| 127 | 190.1 |
| 128 | 193.0 |
| 129 | 195.8 |
| 130 | 198.7 |
| 131 | 201.6 |
| 132 | 204.6 |
| 133 | 207.5 |
| 134 | 210.6 |
| 135 | 213.6 |
| 136 | 216.7 |
| 137 | 219.7 |
| 138 | 222.9 |
| 139 | 226.0 |
| 140 | 229.2 |
| 141 | 232.4 |
| 142 | 235.7 |
| 143 | 239.0 |
| 144 | 242.3 |
| 145 | 245.7 |
| 146 | 249.0 |
| 147 | 252.5 |
| 148 | 255.9 |
| 149 | 259.4 |
| 150 | 262.9 |
| °C | Pressure kPa(g) |
|---|---|
| -40 | -50.1 |
| -39 | -47.4 |
| -38 | -44.5 |
| -37 | -41.5 |
| -36 | -38.4 |
| -35 | -35.2 |
| -34 | -31.8 |
| -33 | -28.3 |
| -32 | -24.7 |
| -31 | -20.9 |
| -30 | -16.9 |
| -29 | -12.9 |
| -28 | -8.6 |
| -27 | -4.2 |
| -26 | 0.3 |
| -25 | 5.1 |
| -24 | 10.0 |
| -23 | 15.1 |
| -22 | 20.3 |
| -21 | 25.8 |
| -20 | 31.4 |
| -19 | 37.2 |
| -18 | 43.3 |
| -17 | 49.5 |
| -16 | 56.0 |
| -15 | 62.6 |
| -14 | 69.5 |
| -13 | 76.6 |
| -12 | 83.9 |
| -11 | 91.5 |
| -10 | 99.3 |
| -9 | 107.3 |
| -8 | 115.6 |
| -7 | 124.2 |
| -6 | 133.0 |
| -5 | 142.0 |
| -4 | 151.4 |
| -3 | 161.0 |
| -2 | 170.8 |
| -1 | 181.0 |
| 0 | 191.5 |
| 1 | 202.2 |
| 2 | 213.3 |
| 3 | 224.7 |
| 4 | 236.3 |
| 5 | 248.3 |
| 6 | 260.7 |
| 7 | 273.3 |
| 8 | 286.3 |
| 9 | 299.6 |
| 10 | 313.3 |
| 11 | 327.3 |
| 12 | 341.7 |
| 13 | 356.4 |
| 14 | 371.6 |
| 15 | 387.0 |
| 16 | 402.9 |
| 17 | 419.2 |
| 18 | 435.9 |
| 19 | 452.9 |
| 20 | 470.4 |
| 21 | 488.3 |
| 22 | 506.6 |
| 23 | 525.3 |
| 24 | 544.5 |
| 25 | 564.1 |
| 26 | 584.1 |
| 27 | 604.6 |
| 28 | 625.6 |
| 29 | 647.0 |
| 30 | 668.9 |
| 31 | 691.2 |
| 32 | 714.1 |
| 33 | 737.5 |
| 34 | 761.3 |
| 35 | 785.7 |
| 36 | 810.5 |
| 37 | 835.9 |
| 38 | 861.8 |
| 39 | 888.3 |
| 40 | 915.3 |
| 41 | 942.8 |
| 42 | 970.9 |
| 43 | 999.6 |
| 44 | 1028.8 |
| 45 | 1058.6 |
| 46 | 1089.0 |
| 47 | 1120.0 |
| 48 | 1151.6 |
| 49 | 1183.8 |
| 50 | 1216.6 |
| 51 | 1250.0 |
| 52 | 1284.1 |
| 53 | 1318.8 |
| 54 | 1354.2 |
| 55 | 1390.2 |
| 56 | 1426.9 |
| 57 | 1464.2 |
| 58 | 1502.3 |
| 59 | 1541.0 |
| 60 | 1580.5 |
| 61 | 1620.6 |
| 62 | 1661.5 |
| 63 | 1703.1 |
| 64 | 1745.4 |
| 65 | 1788.5 |
R-134a PT Chart
°F / psig · Safety class A1 · Single component (HFC)
refrigerantptchart.com
| °F | psig |
|---|---|
| -40 | 14.8" |
| -39 | 14.4" |
| -38 | 13.9" |
| -37 | 13.4" |
| -36 | 13.0" |
| -35 | 12.5" |
| -34 | 12.0" |
| -33 | 11.4" |
| -32 | 10.9" |
| -31 | 10.4" |
| -30 | 9.8" |
| -29 | 9.3" |
| -28 | 8.7" |
| -27 | 8.1" |
| -26 | 7.5" |
| -25 | 6.9" |
| -24 | 6.3" |
| -23 | 5.7" |
| -22 | 5.0" |
| -21 | 4.3" |
| -20 | 3.7" |
| -19 | 3.0" |
| -18 | 2.3" |
| -17 | 1.5" |
| -16 | 0.8" |
| -15 | 0.0 |
| -14 | 0.4 |
| -13 | 0.7 |
| -12 | 1.1 |
| -11 | 1.5 |
| -10 | 1.9 |
| -9 | 2.4 |
| -8 | 2.8 |
| -7 | 3.2 |
| -6 | 3.6 |
| -5 | 4.1 |
| -4 | 4.6 |
| -3 | 5.0 |
| -2 | 5.5 |
| -1 | 6.0 |
| 0 | 6.5 |
| 1 | 7.0 |
| 2 | 7.5 |
| 3 | 8.0 |
| 4 | 8.5 |
| 5 | 9.1 |
| 6 | 9.6 |
| 7 | 10.2 |
| °F | psig |
|---|---|
| 8 | 10.8 |
| 9 | 11.3 |
| 10 | 11.9 |
| 11 | 12.5 |
| 12 | 13.1 |
| 13 | 13.8 |
| 14 | 14.4 |
| 15 | 15.0 |
| 16 | 15.7 |
| 17 | 16.4 |
| 18 | 17.0 |
| 19 | 17.7 |
| 20 | 18.4 |
| 21 | 19.1 |
| 22 | 19.9 |
| 23 | 20.6 |
| 24 | 21.3 |
| 25 | 22.1 |
| 26 | 22.9 |
| 27 | 23.7 |
| 28 | 24.5 |
| 29 | 25.3 |
| 30 | 26.1 |
| 31 | 26.9 |
| 32 | 27.8 |
| 33 | 28.6 |
| 34 | 29.5 |
| 35 | 30.4 |
| 36 | 31.3 |
| 37 | 32.2 |
| 38 | 33.1 |
| 39 | 34.1 |
| 40 | 35.0 |
| 41 | 36.0 |
| 42 | 37.0 |
| 43 | 38.0 |
| 44 | 39.0 |
| 45 | 40.1 |
| 46 | 41.1 |
| 47 | 42.2 |
| 48 | 43.2 |
| 49 | 44.3 |
| 50 | 45.4 |
| 51 | 46.6 |
| 52 | 47.7 |
| 53 | 48.9 |
| 54 | 50.0 |
| 55 | 51.2 |
| °F | psig |
|---|---|
| 56 | 52.4 |
| 57 | 53.6 |
| 58 | 54.9 |
| 59 | 56.1 |
| 60 | 57.4 |
| 61 | 58.7 |
| 62 | 60.0 |
| 63 | 61.3 |
| 64 | 62.7 |
| 65 | 64.0 |
| 66 | 65.4 |
| 67 | 66.8 |
| 68 | 68.2 |
| 69 | 69.7 |
| 70 | 71.1 |
| 71 | 72.6 |
| 72 | 74.1 |
| 73 | 75.6 |
| 74 | 77.1 |
| 75 | 78.7 |
| 76 | 80.2 |
| 77 | 81.8 |
| 78 | 83.4 |
| 79 | 85.0 |
| 80 | 86.7 |
| 81 | 88.4 |
| 82 | 90.0 |
| 83 | 91.8 |
| 84 | 93.5 |
| 85 | 95.2 |
| 86 | 97.0 |
| 87 | 98.8 |
| 88 | 100.6 |
| 89 | 102.5 |
| 90 | 104.3 |
| 91 | 106.2 |
| 92 | 108.1 |
| 93 | 110.0 |
| 94 | 112.0 |
| 95 | 113.9 |
| 96 | 115.9 |
| 97 | 118.0 |
| 98 | 120.0 |
| 99 | 122.1 |
| 100 | 124.2 |
| 101 | 126.3 |
| 102 | 128.4 |
| 103 | 130.6 |
| °F | psig |
|---|---|
| 104 | 132.7 |
| 105 | 135.0 |
| 106 | 137.2 |
| 107 | 139.5 |
| 108 | 141.7 |
| 109 | 144.0 |
| 110 | 146.4 |
| 111 | 148.7 |
| 112 | 151.1 |
| 113 | 153.5 |
| 114 | 156.0 |
| 115 | 158.4 |
| 116 | 160.9 |
| 117 | 163.4 |
| 118 | 166.0 |
| 119 | 168.6 |
| 120 | 171.2 |
| 121 | 173.8 |
| 122 | 176.5 |
| 123 | 179.1 |
| 124 | 181.8 |
| 125 | 184.6 |
| 126 | 187.4 |
| 127 | 190.1 |
| 128 | 193.0 |
| 129 | 195.8 |
| 130 | 198.7 |
| 131 | 201.6 |
| 132 | 204.6 |
| 133 | 207.5 |
| 134 | 210.6 |
| 135 | 213.6 |
| 136 | 216.7 |
| 137 | 219.7 |
| 138 | 222.9 |
| 139 | 226.0 |
| 140 | 229.2 |
| 141 | 232.4 |
| 142 | 235.7 |
| 143 | 239.0 |
| 144 | 242.3 |
| 145 | 245.7 |
| 146 | 249.0 |
| 147 | 252.5 |
| 148 | 255.9 |
| 149 | 259.4 |
| 150 | 262.9 |
Italic " = inches of mercury vacuum. Bold rows: 40 °F and 100 °F. Gauge pressures assume sea-level air (14.7 psia / 101.3 kPa). At altitude your gauge reads higher for the same temperature, about 2.5 psi at 5,000 ft. Reference only: always verify with the manufacturer’s data and your gauges.
R-134a PT Chart
°C / kPa (gauge) · Safety class A1 · Single component (HFC)
refrigerantptchart.com
| °C | kPa(g) |
|---|---|
| -40 | -50.1 |
| -39 | -47.4 |
| -38 | -44.5 |
| -37 | -41.5 |
| -36 | -38.4 |
| -35 | -35.2 |
| -34 | -31.8 |
| -33 | -28.3 |
| -32 | -24.7 |
| -31 | -20.9 |
| -30 | -16.9 |
| -29 | -12.9 |
| -28 | -8.6 |
| -27 | -4.2 |
| -26 | 0.3 |
| -25 | 5.1 |
| -24 | 10.0 |
| -23 | 15.1 |
| -22 | 20.3 |
| -21 | 25.8 |
| -20 | 31.4 |
| -19 | 37.2 |
| -18 | 43.3 |
| -17 | 49.5 |
| -16 | 56.0 |
| -15 | 62.6 |
| -14 | 69.5 |
| -13 | 76.6 |
| -12 | 83.9 |
| -11 | 91.5 |
| -10 | 99.3 |
| -9 | 107.3 |
| -8 | 115.6 |
| -7 | 124.2 |
| -6 | 133.0 |
| -5 | 142.0 |
| °C | kPa(g) |
|---|---|
| -4 | 151.4 |
| -3 | 161.0 |
| -2 | 170.8 |
| -1 | 181.0 |
| 0 | 191.5 |
| 1 | 202.2 |
| 2 | 213.3 |
| 3 | 224.7 |
| 4 | 236.3 |
| 5 | 248.3 |
| 6 | 260.7 |
| 7 | 273.3 |
| 8 | 286.3 |
| 9 | 299.6 |
| 10 | 313.3 |
| 11 | 327.3 |
| 12 | 341.7 |
| 13 | 356.4 |
| 14 | 371.6 |
| 15 | 387.0 |
| 16 | 402.9 |
| 17 | 419.2 |
| 18 | 435.9 |
| 19 | 452.9 |
| 20 | 470.4 |
| 21 | 488.3 |
| 22 | 506.6 |
| 23 | 525.3 |
| 24 | 544.5 |
| 25 | 564.1 |
| 26 | 584.1 |
| 27 | 604.6 |
| 28 | 625.6 |
| 29 | 647.0 |
| 30 | 668.9 |
| 31 | 691.2 |
| °C | kPa(g) |
|---|---|
| 32 | 714.1 |
| 33 | 737.5 |
| 34 | 761.3 |
| 35 | 785.7 |
| 36 | 810.5 |
| 37 | 835.9 |
| 38 | 861.8 |
| 39 | 888.3 |
| 40 | 915.3 |
| 41 | 942.8 |
| 42 | 970.9 |
| 43 | 999.6 |
| 44 | 1028.8 |
| 45 | 1058.6 |
| 46 | 1089.0 |
| 47 | 1120.0 |
| 48 | 1151.6 |
| 49 | 1183.8 |
| 50 | 1216.6 |
| 51 | 1250.0 |
| 52 | 1284.1 |
| 53 | 1318.8 |
| 54 | 1354.2 |
| 55 | 1390.2 |
| 56 | 1426.9 |
| 57 | 1464.2 |
| 58 | 1502.3 |
| 59 | 1541.0 |
| 60 | 1580.5 |
| 61 | 1620.6 |
| 62 | 1661.5 |
| 63 | 1703.1 |
| 64 | 1745.4 |
| 65 | 1788.5 |
Negative kPa(g) = vacuum. Bold rows: 4 °C and 38 °C. Gauge pressures assume sea-level air (14.7 psia / 101.3 kPa). At altitude your gauge reads higher for the same temperature, about 2.5 psi at 5,000 ft. Reference only: always verify with the manufacturer’s data and your gauges.
Get a copy of the R-134a PT chart
Pick an image, a one-page PDF, or a full print. Each one is free, and none of them need an email.
How to use
- Choose Temperature or Pressure and type the number. The answer shows straight away.
- Blends show two values: use vapor (dew) for superheat and liquid (bubble) for subcooling.
- Tap °C · kPa for metric. Below 0 psig, pressure is in inches of mercury (inHg) vacuum.
- Under Get a copy, pick one: Save chart image to phone (PNG) is a picture for your photos; Download 1-page PDF chart (every 5°) is one page of rows every 5°; Print full chart (every 1°, compact layout) prints the full table with a row for every degree, in a compact layout (on a phone, that can also save as a PDF).
About this R-134a chart
This R-134a pressure temperature chart gives the saturation pressure for every degree, in psig with °F or kPa (gauge) with °C. Below 0 psig the °F table shows inches of mercury (inHg) vacuum.
Source: manufacturer and supplier charts (Chemours, Honeywell, Arkema, A-Gas), checked against NIST. Reference only: always verify with the manufacturer’s data and your gauges.
Working with R-134a
In car A/C, R-134a is being replaced by R-1234yf in new vehicles. R-1234yf uses different high- and low-side service fittings (SAE J639), so R-134a hoses, couplers and recovery machines don’t fit, and EPA rules don’t allow adapters.
Source: US EPA, MVAC unique fittings.
R-134a has been used in household refrigerators and freezers, vending machines, stand-alone retail-food units, comfort-cooling and ice-rink chillers, some industrial-process-refrigeration chillers, data-center / computer-room air conditioners, and motor-vehicle air conditioning. Those are historical uses. New products and new systems in many of those sectors are now restricted under the AIM Act Technology Transitions rule, so R-134a is not the default choice for new US equipment.
If the unit has been off long enough to equalize, the gauges should read the saturation pressure for the surrounding temperature. On a 90 °F day that is 104.3 psig. At 100 °F it is 124.2 psig. Those are standing readings, not running high-side targets.
For a sense of the range, not as a target: a 40 °F evaporator is 35.0 psig on this table, a 20 °F evaporator is 18.4 psig, and a 25 °F evaporator is 22.1 psig. Below about −15 °F the chart is in vacuum (inches of mercury, not a negative psig). At −15 °F the table displays 0.0; at −14 °F it is 0.4 psig, so the chart crosses atmospheric pressure between those two rows. On a 90 °F day, a 20 °F condenser approach is a 110 °F saturated condensing temperature, which is 146.4 psig on this table. A 15 °F approach would be 105 °F, or 135.0 psig. Always go by the nameplate, the metering device, and the measured air or water temperatures. For how to convert a gauge reading, see how to read a PT chart. There is no glide, so one saturation pressure works for both superheat and subcooling.
Stationary and commercial R-134a systems typically use POE (polyol ester) oil, which absorbs moisture. Keep the system closed. For cars and trucks, use only the lubricant specified by the vehicle or compressor maker. Do not assume the oil in a vehicle system and the oil in a stationary R-134a system are interchangeable.
The AIM Act exchange value for HFC-134a is 1,430. That sits above the Technology Transitions GWP caps of 150, 300, 700, and 1,400, so new products and new systems that use those caps cannot use R-134a. HFC-134a is also named on some of the rule’s listed-refrigerant rows. SNAP is EPA’s separate substitute-listing program under the Clean Air Act. On the household refrigerators and freezers table, HFC-134a is listed as unacceptable in new equipment as of January 1, 2021. On the cold-storage warehouses table it is still listed as acceptable, but that SNAP cell is not permission to install a new cold-storage system that the AIM rule already restricts.
Selected AIM Technology Transitions dates that apply to this gas are manufacture or import dates for products, and installation dates for systems, under 40 CFR 84.54 as amended by the May 26, 2026 reconsideration, effective July 27, 2026. EPA’s sector tables are informational; for compliance, see 40 CFR part 84, subpart B, § 84.54. Sale or distribution of products is generally restricted three years after the manufacture or import date, so that date is not the last day a unit can be sold.
Product dates: new household refrigerators and freezers, vending machines, and stand-alone retail-food units have a GWP 150 manufacture and import date of January 1, 2025. Comfort-cooling and ice-rink chillers have a GWP 700 date of January 1, 2025. Industrial-process-refrigeration chillers have a GWP 700 date of January 1, 2026 when the exiting fluid is −22 °F (−30 °C) or warmer, and January 1, 2028 when the exiting fluid is between −58 °F and −22 °F (−50 °C to −30 °C). Light-duty motor-vehicle A/C has a GWP 150 date of model year 2025, no earlier than October 24, 2024; medium-duty passenger vehicles and heavy-duty pickup trucks and vans have a model year 2028 date, and listed nonroad vehicles have a January 1, 2028 date. Data-center and computer-room air conditioners have a GWP 700 date of January 1, 2027. Intermodal containers with a box temperature of −31 °F (−35 °C) or warmer have a GWP 700 date of July 27, 2027. Smaller self-contained automatic commercial ice machines have a GWP 150 date of January 1, 2026; larger harvest rates use a named list that includes HFC-134a, from January 1, 2027. Refrigerated food processing and dispensing equipment with a charge of 500 g or less (outside UL 621) has a GWP 150 date of January 1, 2027; some larger equipment and some ice-cream makers use named lists that include HFC-134a.
System dates: new cold-storage warehouse systems have an interim GWP 700 installation date beginning July 27, 2026, then GWP 150 (200 lb or more, excluding the cascade high side) or 300 (under 200 lb, or the cascade high side) on January 1, 2032. New supermarket systems have an interim GWP 1,400 date beginning January 1, 2027, then 150 / 300 on January 1, 2032. New remote condensing units have an interim GWP 1,400 date beginning July 27, 2026, then 150 / 300 on January 1, 2032. HFC-134a’s exchange value of 1,430 is above that 1,400 interim cap. Remote refrigerated food processing and dispensing systems have a named list that includes HFC-134a, from January 1, 2027.
You can typically still service equipment that is already installed. These dates restrict new products and new systems in listed sectors; they are not a blanket ban on servicing existing R-134a equipment, and they are not a service ban on cylinders used on installed equipment.
Sources: 42 U.S.C. § 7675, Table 1; EPA, Technology Transitions HFC restrictions by sector; 91 FR 31284 (effective July 27, 2026); EPA SNAP, household refrigerators and freezers; EPA SNAP, cold storage warehouses.
FAQ
What is the R-134a pressure at 40 °F?
35.0 psig at saturation, from the table above.
What is the R-134a pressure at 100 °F?
124.2 psig at saturation.
Does R-134a have glide?
No. R-134a is a single-component refrigerant, so one saturation pressure works for both superheat and subcooling.
What standing pressure should I see on a 90 °F day?
If the system has been off long enough to equalize, about 104.3 psig, the saturation pressure at 90 °F on this chart. That is a standing reading, not a running high-side target.
What is an example high-side pressure on a 90 °F day?
It depends on the condenser and the airflow or water. As a worked example only, a 20 °F approach is 110 °F saturated condensing temperature, which is 146.4 psig on this chart. Go by the equipment, not this example.
Can I still service existing R-134a equipment?
In general, yes. The AIM Act Technology Transitions dates restrict new products and new systems in listed sectors; they are not a blanket ban on servicing equipment that is already installed. For new light-duty vehicles, R-1234yf uses different SAE J639 fittings, and EPA does not allow adapters.
Coming from Check & Charge or PT Pro? See the free offline alternative (no login).