R-290 PT Chart

R-290 saturation pressure, −60 to 150 °F−50 to 65 °C. Used in self-contained commercial cases and small A/C units.

How to use ↓

Download, share or get updates ↓

Safety class A3Single component (hydrocarbon)No glideNo glide

PT lookup

Step 2 I know the
°F°C

Type a temperature to see the saturation pressure.

R-290 pressure temperature table

Below 0 psig: inches of mercury vacuum. Highlighted: 40 °F and 100 °F. Gauge pressures assume sea-level air (14.7 psia / 101.3 kPa). At altitude your gauge reads higher for the same temperature, about 2.5 psi at 5,000 ft. Negative kPa(g) = vacuum. Highlighted: 4 °C and 38 °C. Gauge pressures assume sea-level air (14.7 psia / 101.3 kPa). At altitude your gauge reads higher for the same temperature, about 2.5 psi at 5,000 ft.

R-290 saturation pressure by temperature, °F and psig (vacuum in inches of mercury)
°FPressure psig
-6010.2 inHg
-599.6 inHg
-589.1 inHg
-578.5 inHg
-568.0 inHg
-557.4 inHg
-546.8 inHg
-536.2 inHg
-525.6 inHg
-514.9 inHg
-504.3 inHg
-493.6 inHg
-483.0 inHg
-472.3 inHg
-461.6 inHg
-450.9 inHg
-440.1 inHg
-430.3
-420.7
-411.0
-401.4
-391.8
-382.2
-372.6
-363.0
-353.4
-343.9
-334.3
-324.8
-315.2
-305.7
-296.1
-286.6
-277.1
-267.6
-258.1
-248.6
-239.1
-229.6
-2110.2
-2010.7
-1911.3
-1811.8
-1712.4
-1613.0
-1513.6
-1414.2
-1314.8
-1215.4
-1116.1
-1016.7
-917.4
-818.0
-718.7
-619.4
-520.1
-420.8
-321.5
-222.2
-122.9
023.7
124.5
225.2
326.0
426.8
527.6
628.4
729.2
830.1
930.9
1031.8
1132.7
1233.6
1334.5
1435.4
1536.3
1637.2
1738.2
1839.2
1940.1
2041.1
2142.1
2243.2
2344.2
2445.2
2546.3
2647.4
2748.5
2849.6
2950.7
3051.8
3153.0
3254.1
3355.3
3456.5
3557.7
3658.9
3760.1
3861.4
3962.7
4063.9
4165.2
4266.5
4367.9
4469.2
4570.6
4672.0
4773.4
4874.8
4976.2
5077.6
5179.1
5280.6
5382.1
5483.6
5585.1
5686.7
5788.2
5889.8
5991.4
6093.0
6194.7
6296.3
6398.0
6499.7
65101.4
66103.1
67104.9
68106.6
69108.4
70110.2
71112.0
72113.9
73115.7
74117.6
75119.5
76121.4
77123.4
78125.4
79127.3
80129.3
81131.4
82133.4
83135.5
84137.6
85139.7
86141.8
87143.9
88146.1
89148.3
90150.5
91152.8
92155.0
93157.3
94159.6
95161.9
96164.3
97166.7
98169.1
99171.5
100173.9
101176.4
102178.9
103181.4
104183.9
105186.5
106189.1
107191.7
108194.3
109197.0
110199.6
111202.4
112205.1
113207.8
114210.6
115213.4
116216.3
117219.1
118222.0
119224.9
120227.8
121230.8
122233.8
123236.8
124239.9
125242.9
126246.0
127249.1
128252.3
129255.5
130258.7
131261.9
132265.2
133268.5
134271.8
135275.1
136278.5
137281.9
138285.4
139288.8
140292.3
141295.8
142299.4
143303.0
144306.6
145310.2
146313.9
147317.6
148321.4
149325.1
150328.9
R-290 saturation pressure by temperature, °C and kPa(g) (negative = vacuum)
°CPressure kPa(g)
-50-30.8
-49-27.3
-48-23.8
-47-20.1
-46-16.2
-45-12.3
-44-8.2
-43-3.9
-420.5
-415.1
-409.8
-3914.7
-3819.7
-3724.9
-3630.3
-3535.9
-3441.6
-3347.6
-3253.7
-3160.0
-3066.5
-2973.2
-2880.1
-2787.2
-2694.6
-25102.1
-24109.9
-23117.9
-22126.1
-21134.5
-20143.2
-19152.1
-18161.3
-17170.7
-16180.4
-15190.3
-14200.5
-13210.9
-12221.7
-11232.7
-10244.0
-9255.5
-8267.4
-7279.5
-6292.0
-5304.7
-4317.8
-3331.1
-2344.8
-1358.8
0373.1
1387.8
2402.8
3418.1
4433.8
5449.8
6466.2
7482.9
8500.0
9517.4
10535.3
11553.5
12572.1
13591.1
14610.4
15630.2
16650.4
17670.9
18691.9
19713.3
20735.1
21757.4
22780.1
23803.2
24826.7
25850.7
26875.2
27900.1
28925.5
29951.4
30977.7
311004.5
321031.8
331059.5
341087.8
351116.6
361145.8
371175.6
381205.9
391236.7
401268.1
411300.0
421332.4
431365.4
441398.9
451433.0
461467.6
471502.9
481538.6
491575.0
501612.0
511649.5
521687.7
531726.5
541765.8
551805.8
561846.5
571887.7
581929.7
591972.2
602015.4
612059.3
622103.9
632149.1
642195.0
652241.6

R-290 PT Chart

°F / psig · Safety class A3 · Single component (hydrocarbon)

refrigerantptchart.com

°Fpsig
-6010.2"
-599.6"
-589.1"
-578.5"
-568.0"
-557.4"
-546.8"
-536.2"
-525.6"
-514.9"
-504.3"
-493.6"
-483.0"
-472.3"
-461.6"
-450.9"
-440.1"
-430.3
-420.7
-411.0
-401.4
-391.8
-382.2
-372.6
-363.0
-353.4
-343.9
-334.3
-324.8
-315.2
-305.7
-296.1
-286.6
-277.1
-267.6
-258.1
-248.6
-239.1
-229.6
-2110.2
-2010.7
-1911.3
-1811.8
°Fpsig
-1712.4
-1613.0
-1513.6
-1414.2
-1314.8
-1215.4
-1116.1
-1016.7
-917.4
-818.0
-718.7
-619.4
-520.1
-420.8
-321.5
-222.2
-122.9
023.7
124.5
225.2
326.0
426.8
527.6
628.4
729.2
830.1
930.9
1031.8
1132.7
1233.6
1334.5
1435.4
1536.3
1637.2
1738.2
1839.2
1940.1
2041.1
2142.1
2243.2
2344.2
2445.2
2546.3
°Fpsig
2647.4
2748.5
2849.6
2950.7
3051.8
3153.0
3254.1
3355.3
3456.5
3557.7
3658.9
3760.1
3861.4
3962.7
4063.9
4165.2
4266.5
4367.9
4469.2
4570.6
4672.0
4773.4
4874.8
4976.2
5077.6
5179.1
5280.6
5382.1
5483.6
5585.1
5686.7
5788.2
5889.8
5991.4
6093.0
6194.7
6296.3
6398.0
6499.7
65101.4
66103.1
67104.9
68106.6
°Fpsig
69108.4
70110.2
71112.0
72113.9
73115.7
74117.6
75119.5
76121.4
77123.4
78125.4
79127.3
80129.3
81131.4
82133.4
83135.5
84137.6
85139.7
86141.8
87143.9
88146.1
89148.3
90150.5
91152.8
92155.0
93157.3
94159.6
95161.9
96164.3
97166.7
98169.1
99171.5
100173.9
101176.4
102178.9
103181.4
104183.9
105186.5
106189.1
107191.7
108194.3
109197.0
110199.6
111202.4
°Fpsig
112205.1
113207.8
114210.6
115213.4
116216.3
117219.1
118222.0
119224.9
120227.8
121230.8
122233.8
123236.8
124239.9
125242.9
126246.0
127249.1
128252.3
129255.5
130258.7
131261.9
132265.2
133268.5
134271.8
135275.1
136278.5
137281.9
138285.4
139288.8
140292.3
141295.8
142299.4
143303.0
144306.6
145310.2
146313.9
147317.6
148321.4
149325.1
150328.9

Italic " = inches of mercury vacuum. Bold rows: 40 °F and 100 °F. Gauge pressures assume sea-level air (14.7 psia / 101.3 kPa). At altitude your gauge reads higher for the same temperature, about 2.5 psi at 5,000 ft. Reference only: always verify with the manufacturer’s data and your gauges.

R-290 PT Chart

°C / kPa (gauge) · Safety class A3 · Single component (hydrocarbon)

refrigerantptchart.com

°CkPa(g)
-50-30.8
-49-27.3
-48-23.8
-47-20.1
-46-16.2
-45-12.3
-44-8.2
-43-3.9
-420.5
-415.1
-409.8
-3914.7
-3819.7
-3724.9
-3630.3
-3535.9
-3441.6
-3347.6
-3253.7
-3160.0
-3066.5
-2973.2
-2880.1
-2787.2
-2694.6
-25102.1
-24109.9
-23117.9
-22126.1
°CkPa(g)
-21134.5
-20143.2
-19152.1
-18161.3
-17170.7
-16180.4
-15190.3
-14200.5
-13210.9
-12221.7
-11232.7
-10244.0
-9255.5
-8267.4
-7279.5
-6292.0
-5304.7
-4317.8
-3331.1
-2344.8
-1358.8
0373.1
1387.8
2402.8
3418.1
4433.8
5449.8
6466.2
7482.9
°CkPa(g)
8500.0
9517.4
10535.3
11553.5
12572.1
13591.1
14610.4
15630.2
16650.4
17670.9
18691.9
19713.3
20735.1
21757.4
22780.1
23803.2
24826.7
25850.7
26875.2
27900.1
28925.5
29951.4
30977.7
311004.5
321031.8
331059.5
341087.8
351116.6
361145.8
°CkPa(g)
371175.6
381205.9
391236.7
401268.1
411300.0
421332.4
431365.4
441398.9
451433.0
461467.6
471502.9
481538.6
491575.0
501612.0
511649.5
521687.7
531726.5
541765.8
551805.8
561846.5
571887.7
581929.7
591972.2
602015.4
612059.3
622103.9
632149.1
642195.0
652241.6

Negative kPa(g) = vacuum. Bold rows: 4 °C and 38 °C. Gauge pressures assume sea-level air (14.7 psia / 101.3 kPa). At altitude your gauge reads higher for the same temperature, about 2.5 psi at 5,000 ft. Reference only: always verify with the manufacturer’s data and your gauges.

Get a copy of the R-290 PT chart

Pick an image, a one-page PDF, or a full print. Each one is free, and none of them need an email.

R-290 PT chart: saturation pressure in psig by °F and kPa by °C

How to use

  1. Choose Temperature or Pressure and type the number. The answer shows straight away.
  2. Blends show two values: use vapor (dew) for superheat and liquid (bubble) for subcooling.
  3. Tap °C · kPa for metric. Below 0 psig, pressure is in inches of mercury (inHg) vacuum.
  4. Under Get a copy, pick one: Save chart image to phone (PNG) is a picture for your photos; Download 1-page PDF chart (every 5°) is one page of rows every 5°; Print full chart (every 1°, compact layout) prints the full table with a row for every degree, in a compact layout (on a phone, that can also save as a PDF).

Back to top ↑

About this R-290 chart

This R-290 pressure temperature chart gives the saturation pressure for every degree, in psig with °F or kPa (gauge) with °C. Below 0 psig the °F table shows inches of mercury (inHg) vacuum.

R-290 refrigerant pressure runs a little below R-22 at the same temperature. The chart starts at -60 °F (10.2 inHg vacuum) for low-temperature propane cases.

Source: supplier charts (A-Gas, National Refrigerants), checked against NIST. Reference only: always verify with the manufacturer’s data and your gauges.

Working with R-290

R-290 is A3 (highly flammable). Charge sizes are small: under EPA SNAP Rule 26, new stand-alone cases built to UL 60335-2-89 can hold up to roughly 500 g if open, about 300 g with doors or drawers, and less near an exit path. Never braze on a charged system, and use spark-free recovery equipment rated for A3. Charge by weight, to the nameplate.

Source: EPA SNAP Rule 26, Federal Register, 13 June 2024.

At 40 °F, R-290 is 63.9 psig. At 100 °F it is 173.9 psig. One number at each temperature: there is no glide, so the same column works for superheat and subcooling. The low end of the table is in vacuum. At −60 °F it is 10.2 inHg; at −40 °F it is already 1.4 psig. The chart and the boiling-points page agree: propane boils just below −43 °F at sea level.

R-290 is not a drop-in or a retrofit for equipment built for R-22 or R-404A. SNAP lists it for new equipment designed and labelled for it. Service a factory R-290 unit to the nameplate, with A3-rated tools. Do not convert an existing HFC or HCFC system to propane.

For a sense of the range, not as a target: a 20 °F evaporator is 41.1 psig on this table, and a 25 °F evaporator is 46.3 psig. On a 90 °F day with a 20 °F condenser TD (110 °F condensing), the table reads 199.6 psig. Those figures are much lower than R-404A or R-410A at the same saturation temperatures, which is one reason the gauges are not a swap.

FAQ

What is the R-290 pressure at 40 °F?

63.9 psig at saturation, from the table above.

What is the R-290 pressure at 100 °F?

173.9 psig at saturation.

Does R-290 have glide?

No. R-290 is a single-component refrigerant, so one saturation pressure works for both superheat and subcooling.

What is the R-290 pressure at 40 °F and at 100 °F?

63.9 psig at 40 °F, 173.9 psig at 100 °F, from the table above. One number at each temperature: R-290 has no glide.

Can I convert an R-22 or R-404A system to R-290?

No. EPA SNAP lists R-290 for new equipment designed and labelled for it, not as a retrofit refrigerant for equipment built for another refrigerant. Charge sizes are also small, and the electrical and tooling rules for an A3 refrigerant are not the same as for A1.

Why does the low end of the chart show inches of mercury?

Below about −43 °F the saturation pressure is below 0 psig (a vacuum relative to sea-level air). The table follows the same convention as the other charts on this site and prints those rows as inHg vacuum. At −60 °F it is 10.2 inHg. At −40 °F it is already 1.4 psig, above atmospheric.

Coming from Check & Charge or PT Pro? See the free offline alternative (no login).

Related