R-744 PT Chart

R-744 saturation pressure, −60 to 87 °F−50 to 30 °C. Used in CO2 transcritical and cascade refrigeration.

How to use ↓

Download, share or get updates ↓

Safety class A1Single component (natural)No glideNo glide

PT lookup

Step 2 I know the
°F°C

Type a temperature to see the saturation pressure.

R-744 pressure temperature table

Highlighted: 40 °F. Gauge pressures assume sea-level air (14.7 psia / 101.3 kPa). At altitude your gauge reads higher for the same temperature, about 2.5 psi at 5,000 ft. Negative kPa(g) = vacuum. Highlighted: 4 °C. Gauge pressures assume sea-level air (14.7 psia / 101.3 kPa). At altitude your gauge reads higher for the same temperature, about 2.5 psi at 5,000 ft.

The table stops just below the critical point (87.76 °F / 30.98 °C, 1055 psig). Above it there is no saturation pressure.

R-744 saturation pressure by temperature, °F and psig (vacuum in inches of mercury)
°FPressure psig
-6079.9
-5982.1
-5884.3
-5786.5
-5688.8
-5591.1
-5493.5
-5395.9
-5298.4
-51100.9
-50103.4
-49106.0
-48108.6
-47111.2
-46113.9
-45116.6
-44119.4
-43122.3
-42125.1
-41128.0
-40131.0
-39134.0
-38137.0
-37140.1
-36143.3
-35146.5
-34149.7
-33153.0
-32156.3
-31159.7
-30163.1
-29166.6
-28170.1
-27173.7
-26177.3
-25181.0
-24184.8
-23188.5
-22192.4
-21196.3
-20200.2
-19204.2
-18208.3
-17212.4
-16216.5
-15220.8
-14225.0
-13229.4
-12233.8
-11238.2
-10242.7
-9247.3
-8251.9
-7256.6
-6261.3
-5266.1
-4271.0
-3275.9
-2280.9
-1285.9
0291.0
1296.2
2301.5
3306.8
4312.1
5317.6
6323.1
7328.6
8334.2
9339.9
10345.7
11351.5
12357.4
13363.4
14369.5
15375.6
16381.8
17388.0
18394.3
19400.7
20407.2
21413.8
22420.4
23427.1
24433.8
25440.7
26447.6
27454.6
28461.7
29468.8
30476.1
31483.4
32490.8
33498.3
34505.8
35513.4
36521.2
37529.0
38536.9
39544.8
40552.9
41561.0
42569.3
43577.6
44586.0
45594.5
46603.1
47611.7
48620.5
49629.3
50638.3
51647.3
52656.5
53665.7
54675.0
55684.4
56694.0
57703.6
58713.3
59723.1
60733.1
61743.1
62753.2
63763.4
64773.8
65784.2
66794.8
67805.5
68816.2
69827.1
70838.1
71849.2
72860.5
73871.8
74883.3
75894.9
76906.7
77918.5
78930.5
79942.6
80954.9
81967.3
82979.8
83992.5
841005.4
851018.4
861031.6
871044.9
R-744 saturation pressure by temperature, °C and kPa(g) (negative = vacuum)
°CPressure kPa(g)
-50581.0
-49609.2
-48638.2
-47668.0
-46698.8
-45730.5
-44763.1
-43796.7
-42831.2
-41866.7
-40903.2
-39940.7
-38979.2
-371018.8
-361059.4
-351101.1
-341143.9
-331187.8
-321232.9
-311279.1
-301326.4
-291375.0
-281424.7
-271475.7
-261527.9
-251581.4
-241636.2
-231692.2
-221749.6
-211808.3
-201868.3
-191929.7
-181992.5
-172056.7
-162122.4
-152189.5
-142258.0
-132328.1
-122399.6
-112472.7
-102547.4
-92623.6
-82701.4
-72780.8
-62861.8
-52944.6
-43028.9
-33115.0
-23202.9
-13292.5
03383.8
13477.0
23572.0
33668.8
43767.5
53868.1
63970.7
74075.2
84181.7
94290.3
104400.9
114513.5
124628.3
134745.3
144864.4
154985.8
165109.5
175235.4
185363.8
195494.5
205627.7
215763.5
225901.8
236042.7
246186.4
256332.9
266482.4
276634.8
286790.5
296949.6
307112.4

R-744 PT Chart

°F / psig · Safety class A1 · Single component (natural)

refrigerantptchart.com

°Fpsig
-6079.9
-5982.1
-5884.3
-5786.5
-5688.8
-5591.1
-5493.5
-5395.9
-5298.4
-51100.9
-50103.4
-49106.0
-48108.6
-47111.2
-46113.9
-45116.6
-44119.4
-43122.3
-42125.1
-41128.0
-40131.0
-39134.0
-38137.0
-37140.1
-36143.3
-35146.5
-34149.7
-33153.0
-32156.3
-31159.7
-30163.1
-29166.6
-28170.1
-27173.7
-26177.3
-25181.0
-24184.8
°Fpsig
-23188.5
-22192.4
-21196.3
-20200.2
-19204.2
-18208.3
-17212.4
-16216.5
-15220.8
-14225.0
-13229.4
-12233.8
-11238.2
-10242.7
-9247.3
-8251.9
-7256.6
-6261.3
-5266.1
-4271.0
-3275.9
-2280.9
-1285.9
0291.0
1296.2
2301.5
3306.8
4312.1
5317.6
6323.1
7328.6
8334.2
9339.9
10345.7
11351.5
12357.4
13363.4
°Fpsig
14369.5
15375.6
16381.8
17388.0
18394.3
19400.7
20407.2
21413.8
22420.4
23427.1
24433.8
25440.7
26447.6
27454.6
28461.7
29468.8
30476.1
31483.4
32490.8
33498.3
34505.8
35513.4
36521.2
37529.0
38536.9
39544.8
40552.9
41561.0
42569.3
43577.6
44586.0
45594.5
46603.1
47611.7
48620.5
49629.3
50638.3
°Fpsig
51647.3
52656.5
53665.7
54675.0
55684.4
56694.0
57703.6
58713.3
59723.1
60733.1
61743.1
62753.2
63763.4
64773.8
65784.2
66794.8
67805.5
68816.2
69827.1
70838.1
71849.2
72860.5
73871.8
74883.3
75894.9
76906.7
77918.5
78930.5
79942.6
80954.9
81967.3
82979.8
83992.5
841005.4
851018.4
861031.6
871044.9

Bold rows: 40 °F. Gauge pressures assume sea-level air (14.7 psia / 101.3 kPa). At altitude your gauge reads higher for the same temperature, about 2.5 psi at 5,000 ft. Table stops below the critical point. Reference only: always verify with the manufacturer’s data and your gauges.

R-744 PT Chart

°C / kPa (gauge) · Safety class A1 · Single component (natural)

refrigerantptchart.com

°CkPa(g)
-50581.0
-49609.2
-48638.2
-47668.0
-46698.8
-45730.5
-44763.1
-43796.7
-42831.2
-41866.7
-40903.2
-39940.7
-38979.2
-371018.8
-361059.4
-351101.1
-341143.9
-331187.8
-321232.9
-311279.1
-301326.4
-291375.0
-281424.7
-271475.7
-261527.9
-251581.4
-241636.2
°CkPa(g)
-231692.2
-221749.6
-211808.3
-201868.3
-191929.7
-181992.5
-172056.7
-162122.4
-152189.5
-142258.0
-132328.1
-122399.6
-112472.7
-102547.4
-92623.6
-82701.4
-72780.8
-62861.8
-52944.6
-43028.9
-33115.0
-23202.9
-13292.5
03383.8
13477.0
23572.0
33668.8
°CkPa(g)
43767.5
53868.1
63970.7
74075.2
84181.7
94290.3
104400.9
114513.5
124628.3
134745.3
144864.4
154985.8
165109.5
175235.4
185363.8
195494.5
205627.7
215763.5
225901.8
236042.7
246186.4
256332.9
266482.4
276634.8
286790.5
296949.6
307112.4

Bold rows: 4 °C. Gauge pressures assume sea-level air (14.7 psia / 101.3 kPa). At altitude your gauge reads higher for the same temperature, about 2.5 psi at 5,000 ft. Table stops below the critical point. Reference only: always verify with the manufacturer’s data and your gauges.

Get a copy of the R-744 PT chart

Pick an image, a one-page PDF, or a full print. Each one is free, and none of them need an email.

R-744 PT chart: saturation pressure in psig by °F and kPa by °C

How to use

  1. Choose Temperature or Pressure and type the number. The answer shows straight away.
  2. Blends show two values: use vapor (dew) for superheat and liquid (bubble) for subcooling.
  3. Tap °C · kPa for metric. Below 0 psig, pressure is in inches of mercury (inHg) vacuum.
  4. Under Get a copy, pick one: Save chart image to phone (PNG) is a picture for your photos; Download 1-page PDF chart (every 5°) is one page of rows every 5°; Print full chart (every 1°, compact layout) prints the full table with a row for every degree, in a compact layout (on a phone, that can also save as a PDF).

Back to top ↑

About this R-744 chart

This R-744 pressure temperature chart gives the saturation pressure for every degree, in psig with °F or kPa (gauge) with °C.

Source: supplier chart (A-Gas), checked against NIST. Reference only: always verify with the manufacturer’s data and your gauges.

Working with R-744

The table stops at 87 °F (30 °C), just below the critical point at 87.76 °F / 30.98 °C, 1,055 psig (1,070 psia). There is no 90 °F or 100 °F row, and you should not invent one. Above the critical temperature there is no saturation pressure and no condenser in the usual sense. The high side is a gas cooler, and high-side pressure is set by the high-pressure valve and the controller, not by this chart. The low side (the evaporator) is still below the critical point, so the table still applies there.

Standstill pressures are already high while the plant is still below critical. If the system has soaked out to the air temperature, the table reads 838.1 psig at 70 °F, 954.9 psig at 80 °F, and 1,031.6 psig at 86 °F. If the space is above 87.8 °F, you are past the saturation curve. Relief and vessel ratings come from the nameplate, not from this page. Tools and hoses must be rated for the pressure in front of you. A standard R-410A gauge set is not a transcritical high-side tool.

R-744 has no boiling point at 1 atm (0 psig). At sea-level pressure it is a solid: dry ice sublimes at −109.2 °F / −78.5 °C. Liquid CO2 only exists above the triple point, −69.8 °F at 60.4 psig (75 psia, 5.18 bar abs). That is why this chart starts at −60 °F already at 79.9 psig. R-744 is a single-component refrigerant with no glide, so one pressure works for both superheat and subcooling.

FAQ

What is the R-744 pressure at 40 °F?

552.9 psig at saturation, from the table above.

Why does the R-744 table stop at 87 °F?

The table stops just below the critical point (87.76 °F / 30.98 °C, 1055 psig). Above it there is no saturation pressure.

Does R-744 have glide?

No. R-744 is a single-component refrigerant, so one saturation pressure works for both superheat and subcooling.

What happens above the 87 °F end of the R-744 chart?

The critical point is 87.76 °F (30.98 °C), 1,055 psig (1,070 psia). Above that temperature there is no saturation pressure to put on a PT chart. On a hotter day the high side of a transcritical system is a gas cooler, and high-side pressure is controlled, not read from this table. The 87 °F row is 1,044.9 psig, the last whole degree below critical.

What is a normal standstill pressure for CO2 on a warm day?

If the plant has soaked out to the air temperature and is still below the critical point, read the table: 838.1 psig at 70 °F, 954.9 psig at 80 °F, 1,031.6 psig at 86 °F. That is already a much higher standing pressure than R-410A or R-404A. If the space is above 87.8 °F, you are past the saturation curve; do not look for a 90 °F row. Relief and vessel ratings come from the nameplate, not from this paragraph.

Does R-744 have a boiling point at 0 psig, like R-22?

No. At 1 atm, carbon dioxide is a solid. Dry ice goes straight to vapor at −109.2 °F (−78.5 °C). Liquid CO2 only exists above the triple point, −69.8 °F at about 60.4 psig (75 psia). That is why this chart starts at −60 °F already at 79.9 psig, well above atmospheric.