R-404A pressures on walk-in coolers and freezers: what the PT chart says

On R-404A, a walk-in cooler coil running at 25 °F reads about 62 psig, and a walk-in freezer coil at -20 °F reads about 16 psig. Those are the coil temperatures the standard rating test uses for a 35 °F cooler and a -10 °F freezer. On the liquid side, 105 °F works out to about 254 psig.

Use them as a sanity check, not a target. They come from a lab test, and the unit's own data and the manufacturer's charging guidance decide what's normal for the box in front of you. Any other temperature is one tap away on the R-404A PT chart.

Where those numbers come from

Walk-in refrigeration systems sold in the US are rated under AHRI Standard 1250, and the federal energy test for them (10 CFR Part 431, Subpart R) is built on it. The unit cooler tests fix the air going into the coil and the refrigerant coming out of it:

Walk-in rating test conditions and R-404A pressures
Rating testCoolerFreezer
Air entering the coil35 °F-10 °F
Suction dew point at the coil outlet25 °F-20 °F
R-404A suction pressure (dew)62.1 psig16.0 psig
Liquid feed (bubble point)105 °F105 °F
R-404A liquid pressure (bubble)254.2 psig254.2 psig
Liquid subcooling9 °F9 °F

Test conditions from AHRI 1250-2020, Tables 16 and 17. Pressures from this site's R-404A data. Reference only: check the equipment data plate and the manufacturer's data, and verify with your gauges.

Look at the gap between the air and the coil. It's 10 °F in both tests. That's why the suction gauge on a 35 °F box reads nowhere near the 77 psig on the chart's 35 °F row. The coil has to run colder than the air it's cooling.

The same standard rates condensing units on their own at a suction dew point of 23 °F for coolers and -22 °F for freezers, measured where the suction line enters the unit. On R-404A those are 59.3 and 14.6 psig. Keep in mind where your gauge is, too. A gauge at the condensing unit reads after the suction line, so it sits a little below what the coil outlet sees.

R-404A rows for walk-in work

Low side, dew column (use it for suction and superheat):

R-404A low side, dew column
Coil temp (°F)Dew (psig)
-309.6
-2512.7
-2016.0
-1519.7
-1023.6
1549.0
2055.3
2562.1
3069.3

High side, bubble column (use it for liquid and subcooling):

R-404A high side, bubble column
Condensing temp (°F)Bubble (psig)
90204.5
100236.8
105254.2
110272.5
120312.0

R-404A is a blend, but its glide is small, under 1 °F at 40 °F, so the two columns sit close. At 25 °F they're 1.3 psi apart. Read the right one anyway. The habit pays off on blends where the gap is big.

Two superheat checks and a subcooling check

Cooler. The suction reads 60 psig and the clamp on the suction line at the coil outlet reads 31 °F. 60 psig on the dew column is 23.5 °F, so superheat is 7.5 °F.

Freezer. 15 psig with a -15 °F suction line. 15 psig is -21.5 °F on the dew column, so superheat is 6.5 °F.

Liquid line. 254 psig with a 96 °F liquid line. 254 psig is 104.9 °F on the bubble column, so subcooling is 8.9 °F. That happens to be close to the 9 °F the rating test feeds the coil with.

Is 7.5 °F right for that cooler? The chart can't tell you. Even the rating standard tells the lab to set superheat from the equipment's manual, and only uses a default of 6.5 °F when the manual gives none. Go by the valve or controller setting in the unit's documentation. If you'd rather not subtract on a ladder, the superheat and subcooling calculator does it and picks the right column.

Make sure it's really R-404A

Some R-404A boxes get converted to another refrigerant, so read the data plate and look for a retrofit label before you trust the chart. The numbers don't carry over. Say the suction gauge reads 62 psig. On R-404A that's 24.9 °F. On R-448A it's 33.3 °F on the dew column. Use the R-404A chart on an R-448A system and your superheat comes out about 8 °F too high.

R-507A is closer, but not the same. At 25 °F it reads 65.2 psig against 62.1 for R-404A. Use the R-448A PT chart or the R-507A PT chart when that's what's in the system. For the method behind all of this, see how to read a PT chart.

Affiliate link: we may earn a commission if you sign up, at no extra cost to you.

Readings like these are worth writing down on every visit, so the next tech can see what the box ran at last time. If you're looking for software to keep service records and invoices in, Jobber (opens in a new tab) is the one we link to. It has a 14-day free trial, and signing up through our link takes 20% off your first 6 months.

What should R-404A suction pressure be on a walk-in cooler?

It depends on the unit, so check its data first. At the standard rating point for a 35 °F cooler, the coil runs at 25 °F, which is 62.1 psig on the R-404A dew column.

What should R-404A suction pressure be on a walk-in freezer?

At the standard rating point for a -10 °F freezer, the coil runs at -20 °F, which is 16.0 psig on the R-404A dew column. The unit's own data decides what's normal for it.

Do I read the dew or bubble column for R-404A?

Dew for suction pressure and superheat, bubble for liquid pressure and subcooling. On R-404A the two are only about a psi apart at walk-in temperatures, but reading the right column keeps the habit for blends with more glide.