On a 90 °F day, an R-22 unit that has been off long enough to equalize, and still has liquid and vapor in it, should stand close to 168.4 psig. That is the saturation pressure at 90 °F, not the head pressure you will see once the compressor is running.
Those two ideas get mixed up a lot. Outdoor air is not condensing temperature on a running unit. This page walks through both numbers, and how to turn a condenser temperature difference into a high-side reading. It is not a charging chart. Charge from the manufacturer's data, with airflow confirmed, on a running system. Any other temperature is one tap away on the R-22 PT chart. The method is the same as on the R-410A pressures on a 90 °F day article; the numbers are not. Do not swap charts.
Standing pressure is the 90 °F row, with caveats
If pressures have equalized and the coil and piping have soaked out to the surrounding air, standing (static) pressure should sit close to the 90 °F row: 168.4 psig. That is saturation physics, not a charging method. The row is the saturation pressure at 90 °F, nothing more. R-22 is a single-component refrigerant, so there is one number, not a liquid and vapor pair.
| Temperature (°F) | Pressure (psig) |
|---|---|
| 70 | 121.4 |
| 80 | 143.6 |
| 90 | 168.4 |
| 95 | 181.8 |
| 100 | 195.9 |
A few things have to be true, or the gauge will not match that row:
- Equalized and soaked. A unit that just shut off, or was just started, is not standing pressure. Give it time. Parts of a split system can sit at different temperatures. The pressure you read is one system pressure. It tracks the two-phase region, which is usually the coldest place the charge has migrated to, not necessarily the thermometer in the shade.
- Liquid and vapor both have to be present. Saturation pressure only applies when a two-phase mixture is still in the system. A severe undercharge, or a lost charge, can stand below the saturation pressure for the air temperature. Do not treat a low standing pressure as "the air is cooler than I thought" without checking charge and leaks.
- Sun-loaded coils read high. A condenser sitting in direct sun can be well above shaded outdoor air. Standing pressure then sits above the 90 °F row even though the weather app says 90 °F. The same happens with a coil in a hot doghouse or on a black roof.
A standing pressure close to the 90 °F row does not mean the charge is right. It only means the system can still make a saturation pressure at that temperature. Do not treat 168.4 psig as "the" operating pressure on a 90 °F day.
Running head is outdoor air plus condenser TD
Once the unit is running, condensing temperature is outdoor (entering-air) dry bulb plus the condenser’s actual temperature difference, or TD. Air-cooled condensers are commonly selected in a 10–30 °F TD range. A 20 °F TD is a fair worked example. On a 90 °F day that example is a 110 °F condensing temperature, which is 226.4 psig on the live R-22 table.
| Assumed TD | Condensing temp | Pressure (psig) |
|---|---|---|
| 15 °F | 105 °F | 210.8 |
| 20 °F | 110 °F | 226.4 |
| 25 °F | 115 °F | 242.8 |
That table is not a promise, and 226 psig is not "the" running pressure on a 90 °F day. A larger condenser, or one running below design load, will run a lower TD. A dirty coil, a failing fan, or recirculated discharge air will run a higher TD. The 10–30 °F range and the 20 °F example come from Copeland Refrigeration Manual, Part 3, AE-103, and a 20 °F example also appears in Heatcraft bulletin BN-RACCTG (September 2022). The same range and method are used in the R-410A 90 °F article; only the pressures change.
Do not attach a SEER number to a TD, and do not treat a single high-side reading as proof that the charge is right or wrong.
R-22 is one column, still not a target
R-22 (chlorodifluoromethane) is a single-component HCFC, ASHRAE 34 safety class A1. The table is one saturation pressure, from −40 to 150 °F. There is no dew vs bubble split and no meaningful glide. The same number works for both superheat and subcooling. That still does not make the 90 °F row a running head, or a suction target. At a 40 °F evaporator, a typical comfort-cooling example, the table is 68.6 psig.
Superheat and subcooling, without a target from this chart
Fix airflow first (filter, coil, blower, supply and return). Then calculate superheat or subcooling from the one R-22 column:
- Superheat = suction line temperature minus saturation temperature at the suction pressure.
- Subcooling = saturation temperature at the liquid pressure minus liquid line temperature.
Whether the result is right comes from the equipment charging chart (TXV versus fixed orifice, indoor wet bulb, outdoor dry bulb), not from the PT chart. This page does not publish a superheat or subcooling target. If you would rather not subtract on a ladder, the superheat and subcooling calculator does the math. The method is in how to read a PT chart.
How this compares with R-410A
R-22 runs much lower than R-410A at the same temperatures. These are the matching saturation rows from this site's tables, not running targets. The R-410A figures are dew on the low side and bubble on the high side, which is how you use those columns on the job. The full walkthrough is on the R-410A pressures on a 90 °F day article.
| Refrigerant | 40 °F evap | Standing at 90 °F | 110 °F (20 °F TD example) |
|---|---|---|---|
| R-22 | 68.6 | 168.4 | 226.4 |
| R-410A | 118.4 dew | 275.4 / 274.5 | 366.4 bubble |
Close enough to look familiar is not close enough to swap charts, oils, or hoses. Do not charge an R-22 system with R-410A, or the other way around. Use the R-22 PT chart when that is what is on the data plate.
Servicing R-22 after the 2020 phaseout
New R-22 production and import ended in the US on January 1, 2020. Systems are serviced with reclaimed R-22 or R-22 made before 2020. Recovered R-22 can go back into equipment of the same owner; it must be reclaimed by an EPA-certified reclaimer before it’s sold to anyone else. Mineral oil (sometimes alkylbenzene) is standard; when retrofitting to an HFC blend, check the blend maker’s oil guidance.
If you do convert the system, that work is a retrofit, not a drop-in. For one common R-22 retrofit blend, see the notes on the R-449A PT chart and go by the blend maker's guide and the compressor OEM. This page is not a replacement catalog.
Source: US EPA, HCFC phaseout fact sheet and technician FAQ on recovered refrigerant.
Sources
Pressures are from this site's live tables, which match the published rows on the R-22 PT chart. The condenser TD range and the 20 °F worked example are from Copeland Refrigeration Manual, Part 3, AE-103, and from Heatcraft BN-RACCTG, "Air Cooled Condensers," September 2022. Reference only: always verify with the manufacturer's data and your gauges.
Affiliate link: we may earn a commission if you sign up, at no extra cost to you.
Readings like these are worth writing down on every visit, so the next tech can see what the unit ran at last time. If you're looking for software to keep service records and invoices in, Jobber (opens in a new tab) is the one we link to. It has a 14-day free trial, and signing up through our link takes 20% off your first 6 months.
What is a good R-22 pressure on a 90 °F day?
Standing (static) pressure, if the system has equalized and soaked out to 90 °F air and still has a two-phase charge, should sit close to 168.4 psig. That is the saturation pressure at 90 °F, not a running suction or head target, and not a charge diagnosis by itself.
What should R-22 head pressure be on a 90 °F day?
Condensing temperature is outdoor dry bulb plus the condenser’s actual TD. Air-cooled condensers are commonly selected in a 10–30 °F TD range. A 20 °F example on a 90 °F day is 110 °F, which is 226.4 psig on this site's table. A dirty coil or a failing fan will run higher; a lightly loaded condenser will run lower. This page does not publish a single “normal” running pressure.
Does R-22 have two columns, like R-410A?
No. R-22 is a single-component refrigerant. One saturation pressure is used for both superheat and subcooling.
Can I use the R-410A chart on an R-22 unit?
No. At 90 °F the R-22 row is 168.4 psig; R-410A stands at 275.4 / 274.5 psig. Use the R-22 chart, and open the R-410A 90 °F-day article if that is the refrigerant in the system.
Is new R-22 still being made?
New production and import ended in the US on January 1, 2020. Service uses reclaimed R-22 or R-22 made before 2020, under the EPA rules in “Working with R-22” on the R-22 PT chart.