R-454B vs R-410A pressures: what changes on the gauges

R-454B reads lower than R-410A at the same saturation temperature. With a 40 °F evaporator, R-454B is 107.0 psig on the vapor (dew) column and R-410A is 118.4 psig. Condensing at 100 °F, R-454B is 300.8 psig on the liquid (bubble) column and R-410A is 318.5 psig.

So if the suction on a new unit looks about 11 psi light next to what you're used to, read the nameplate before you go looking for a problem. Every row for both columns is on the R-454B PT chart, and the superheat and subcooling calculator has R-454B in its list, so it will pick the right column for you.

Side by side, from this site's tables

These are saturation pressures, not running targets. Low-side rows matter on the dew column, high-side rows on the bubble column.

R-454B and R-410A saturation pressures (psig)
Temp (°F)R-454B liquid (bubble)R-454B vapor (dew)R-410A liquid (bubble)R-410A vapor (dew)
35101.596.9107.7107.3
40112.0107.0118.8118.4
45123.1117.8130.6130.1
50135.0129.3143.2142.6
95279.9270.4296.4295.5
100300.8290.9318.5317.6
105322.8312.5341.9340.9
110345.9335.2366.4365.4
120395.7384.3419.4418.3

The gap grows as the temperature climbs. It's about 11 psi on the 40 °F suction row (dew against dew) and about 18 psi at 100 °F on the liquid column. The pattern feels familiar. The numbers don't match, so the charts don't swap.

The two columns finally mean something

On R-410A you could get away with reading the wrong column. The 40 °F row is 118.8 and 118.4 psig, under half a psi apart, and the glide is 0.19 °F.

R-454B is a blend of R-32 and R-1234yf (68.9/31.1 by mass) with more glide: 2.34 °F at a 40 °F evaporator on this site's chart. On the 40 °F row the columns are 112.0 and 107.0 psig, about 5 psi apart. Use dew (vapor) for suction pressure and superheat. Use bubble (liquid) for liquid pressure and subcooling.

Get it backwards on the low side and it costs you a couple of degrees. A 107.0 psig suction is 40.0 °F on the dew column but 37.7 °F on the bubble column, so a real 10.0 °F of superheat (with a 50 °F suction line) reads as 12.3.

The bigger mistake: R-454B gauges, R-410A chart

This one is worse. Look up an R-454B reading on an R-410A chart and the saturation temperatures come back wrong.

Take an R-454B system running 107.0 psig suction with a 50 °F suction line, and 300.8 psig liquid with a 90 °F liquid line:

Same R-454B readings, two charts
ReadingOn the R-454B chartOn the R-410A chart
Suction saturation at 107.0 psig40.0 °F (dew)34.8 °F
Superheat, 50 °F suction line10.0 °F15.2 °F
Liquid saturation at 300.8 psig100.0 °F (bubble)96.0 °F
Subcooling, 90 °F liquid line10.0 °F6.0 °F

Superheat reads about 5 °F high and subcooling about 4 °F low. Together that looks like a system short of charge. Nothing is wrong with the system. The chart is wrong.

Read the pressure, look it up on the R-454B chart, and do the subtraction (or let the calculator do it).

R-454B is classed A2L (lower flammability), where R-410A is A1. Use tools and recovery equipment rated for A2L, and follow the equipment manufacturer's instructions and your local code.

Reference only. Check the equipment data plate and the manufacturer's charging data, and verify with your gauges. The method for turning a pressure into superheat or subcooling is in how to read a PT chart, and the full R-410A table is on the R-410A PT chart.

Does R-454B run at lower pressure than R-410A?

At the same saturation temperature, yes. On the 40 °F row the dew column is 107.0 psig for R-454B and 118.4 psig for R-410A. At 100 °F the bubble column is 300.8 psig for R-454B and 318.5 psig for R-410A. These are saturation pressures from this site's tables, not running targets.

Can I use an R-410A PT chart for R-454B?

No. A 107.0 psig R-454B suction is 40.0 °F saturated on the R-454B dew column but 34.8 °F on the R-410A chart. That error adds about 5 °F to superheat, and on the liquid side it takes about 4 °F off subcooling.

Which column do I use for R-454B superheat?

Dew (vapor) for suction pressure and superheat, bubble (liquid) for liquid pressure and subcooling. On the 40 °F row the two columns are about 5 psi apart (112.0 and 107.0 psig), so the right column counts for more than it did on R-410A.